In a CNG station project the three subjects that get discussed most are the compressor, the storage and the dispenser. The dryer usually sits at the bottom of the list. Yet the water carried in the gas is the component that damages the most expensive parts of the station and stops filling in winter. This guide explains why dew point is judged at the compressor outlet, and what separates the three levels of natural gas dryer.
The moisture content of natural gas is described by its water dew point: the temperature at which the gas begins to release water at a given pressure. The design rule for a station is clear. The water dew point of the natural gas at the outlet of the filling station should be sufficiently below the lowest ambient temperature at which the station operates.
There is one detail that is easy to miss here, and it is the effect of compression. On a given pipeline the dew point of the gas can be extremely low when it reaches the compressor, while that value will be significantly higher as the gas leaves the compressor. Looking at a pipeline analysis and assuming the gas is already dry is therefore misleading. The criterion is not the compressor inlet but the station outlet.
Water that condenses at high pressure creates two separate problems, and both affect parts far more expensive than the dryer.
The first is corrosion. Condensed water, together with the other components present in the gas, creates an aggressive environment on the inner surface of the pipework, the storage cylinders and the vehicle cylinders. This is damage that is invisible from the outside and progresses over years.
The second is freezing. High pressure gas expands at the dispenser and as it passes into the vehicle cylinder, and it cools as it expands. Water carried in the gas drops out at that point as ice or hydrate, causing blockages on valves, regulators and the nozzle. This is why dryer capacity is selected for the lowest temperature at which the station operates in winter, not for its summer conditions.
Natural gas dryers are offered at three levels according to the flow rate of the station and its tolerance for downtime. All three are available in the dryer product group.
This is the low cost, low capacity basic package. It requires external regeneration or replacement of the desiccant material. It suits low to medium flows and a low to high pressure design, and is recommended for stations with low volume filling requirements.
This is a rugged, skid mounted series of column regenerating natural gas dryers. The regeneration cycles are closed loop, operator activated and heat reactivated, and the system signals when regeneration is required. It suits medium to high flows and a low to high pressure design, is recommended for average volume filling requirements, and keeps downtime to a minimum.
This version is designed and built for medium to large flows and uninterrupted service cycles. Desiccant regeneration is fully automatic, which maximises dew point performance and energy efficiency. Because an additional drying column takes over whenever regeneration is required, the system has no downtime.
Three questions settle the decision:
The dryer is not a standalone accessory. It is part of the same chain as the compressor and the gas storage. The most common mistake in the field is to increase station capacity and leave the dryer as it is. Once the compressor is replaced and the flow increases, the existing dryer starts working outside its design range; the dew point rises and the problem appears not as a dryer fault but as complaints coming from the dispenser side.
The same logic applies in the other direction. A dryer selected far larger than required means unnecessary investment and unnecessary energy consumption during regeneration. The sound approach is to size the dryer against the current flow of the station together with the capacity planned for the near term.
A dryer is not equipment that looks after itself once installed. A short routine is enough:
2A Engineering supplies CNG compressors, dryers, gas storage systems, dispensers and the remaining station equipment as a single chain, and supports station projects with its service network.
The water dew point of the gas at the station outlet should be sufficiently below the lowest ambient temperature at which the station operates. If pipeline gas does not satisfy that condition at the compressor outlet, a dryer is required.
Compression raises the dew point. A value that is extremely low at the compressor inlet becomes significantly higher at the outlet, so the assessment is made on the outlet rather than the inlet.
The two column version has an additional drying column that takes over when regeneration is required, so no downtime occurs. With single column solutions there is a stop during regeneration or desiccant replacement.
Water that condenses at high pressure causes corrosion in the pipework, the storage cylinders and the vehicle cylinders, and it forms ice or hydrate at the expansion point in the dispenser, leading to blockages.
Flow rate, working pressure, daily filling volume, the station's tolerance for downtime and the lowest ambient temperature of the region. A selection made without these five figures ends up either undersized or oversized.