The storage tank is the part of an LPG station that is decided first and changed last. Its size, its position on the plot and the way it is installed shape everything that follows: safety distances, delivery logistics, pump performance and the licence file. This guide summarises how station storage tanks are classified, where they may be placed and what has to be done at installation.

What an LPG storage tank is

An LPG storage tank is a steel pressure vessel closed to the atmosphere, built to hold LPG in liquid form. It is not a container in the general sense and it is not interchangeable with vessels used for other fuels. Tanks are usually grouped by water capacity:

  • Pressure vessels with a total water capacity below 15 m³.
  • Pressure vessels with a total water capacity between 15.1 m³ and 110 m³.

The capacity decision is not only about turnover. A larger tank reduces the number of deliveries and gives the station room to buy at better moments, but it increases the required safety distances and the footprint of the installation. A smaller tank fits tighter plots but ties the station to more frequent tanker visits.

Aboveground, underground and mounded tanks

Three installation types are used at stations, and each has its own rules.

Aboveground tanks

These sit above ground level on all sides. The complete surface should be painted with white paint that reflects sunlight, which limits heating and pressure rise inside the vessel. Aboveground tanks are fixed on a load bearing concrete base, seated from the two legs at the front or rear in accordance with the standards.

Underground tanks

The upper surface of the body sits below ground, while the tank cover remains partially above ground so that fittings stay accessible. The top surface of the body should be between 15 cm and 30 cm below ground level, and measures must be taken against damage from abrasion, vehicle traffic or other causes.

Mounded tanks

These are above ground level or partially underground and covered on all sides with at least 30 cm of soil, sand or similar non flammable and non corrosive material. The covering protects the vessel thermally and mechanically while keeping the installation outside the building envelope.

One rule applies to all three types: LPG storage tanks are never placed inside buildings, nor on roofs or terraces.

Safety distances and layout

The position of the tank is governed by minimum safety distances to the nearest buildings or groups of buildings, and by the distance of tanks to one another where more than one vessel is installed. These distances are measured, not estimated, and the tank area has to be laid out so that they are respected in every direction.

Layout planning is also the moment to think about the rest of the installation. The suction line to the transfer pump is shorter and more stable when the tank position is chosen with the pump room in mind, and the vapour return line from the dispenser has to run back to the tank without any valve that can be left closed. Decisions made on the drawing save years of operational problems.

Installation requirements that are easy to miss

Grounding

Aboveground tanks and evaporators must be grounded, and the resistance value of that connection is what shows whether the grounding is good. Grounding serves two purposes: discharging static charges that accumulate on the surface under atmospheric conditions, so that they cannot create a spark, and preventing an electrical leak to the body in installations that contain electrical devices. The measurement is made with a megger meter. Where flanges meet, conductive material such as copper sheet should be used between the two flange surfaces to maintain electrical continuity.

Corrosion protection

Underground tanks require cathodic protection against corrosion. Before the vessel is lowered into the pit, its painting and coating must be inspected; if any damage is found, assembly should not proceed until it has been repaired. A coating defect that is invisible after burial becomes an expensive problem years later.

Anchoring

Underground tanks are anchored to a suitable load bearing concrete block, fixed from four points. Anchoring matters because an empty or partly empty buried vessel in waterlogged ground behaves very differently from a full one.

Station tanks and vehicle tanks are not the same subject

Because the words overlap, the two are often confused. Vehicle LPG tanks are a separate product family with their own standards: cylinder and toroidal types, steel sheets typically 3 to 4 mm thick joined with x ray inspected seam welding, compliance with ECE R67, and a defined service life after which the tank must be withdrawn and destroyed. On the vehicle side the critical assembly detail is the multi valve, which must sit with its indicator in the horizontal position and which controls excess flow through its overflow valve.

A station project deals with the first group. A conversion workshop deals with the second. Mixing the two leads to questions that have no sensible answer, such as applying vehicle service life rules to a buried station vessel.

Operating the tank area

Once the station is running, the tank area needs a short, repeatable routine rather than occasional attention: keep the safety distance zone clear, check that white paint on aboveground vessels is intact, confirm grounding connections and measured resistance at planned intervals, inspect the covering of mounded tanks after heavy rain, and keep the return line path free. None of these require special equipment. They require a schedule.

2A Engineering supplies LPG storage tanks together with dispensers, pumps, meters and the remaining station equipment, and supports station projects with its service network.

Deciding the tank capacity

The capacity decision is often made simply by taking the largest tank the plot will allow. A sounder approach is to look at the daily sales estimate and the delivery logistics together: how many days of stock the average daily sale corresponds to, how often a tanker can reach the station, and how much demand rises in the busy season.

Three further points belong in the calculation. The first is safety distances: a larger tank also increases the distance required to buildings and to neighbouring vessels, and reduces the usable area on the plot. The second is the refill window: the tank should be planned so that it never runs completely empty, leaving a margin against delivery delays. The third is future investment: if cylinder filling or fleet filling may be added alongside the autogas operation, tank capacity should be selected with that scenario in mind.

Finally, access around the tank matters as much as its position. A layout where the tanker can manoeuvre, approach the filling point safely and where an emergency team can reach the area is one of the most expensive things to correct after the project is built.

Frequently asked questions

Can an LPG storage tank be placed inside a building?

No. Storage tanks are never installed inside buildings or in places such as roofs and terraces. They are placed outdoors in accordance with the minimum safety distances.

How deep is an underground tank buried?

The top surface of the tank body should be between 15 cm and 30 cm below ground level, with the tank cover remaining partially above ground and with precautions taken against damage from traffic and abrasion.

What makes a mounded tank different?

A mounded tank is covered on all sides with at least 30 cm of non flammable and non corrosive material such as soil or sand, while remaining above ground level or only partially underground.

Why are aboveground tanks painted white?

White paint reflects sunlight and limits the heating of the vessel surface, which helps keep the pressure inside the tank stable.

Is cathodic protection required for every tank?

It is required for underground tanks, where the vessel is in contact with soil and exposed to corrosion that cannot be inspected visually after installation.